Loop Impedance
|
|
Function
|
L-PE ATT OFF
|
L-PE ATT ON
|
L-N / L-L
|
|
Rated Voltage
|
230V (50/60Hz)
|
L-N: 230V (50/60Hz) L-L: 400V (50/60Hz)
|
|
Operating Voltage
|
100 - 280V (45 - 65Hz)
|
100 - 500V (45 - 65Hz)
|
|
Range (Auto-Ranging)
|
20/200/2000Ω
|
20/200/2000Ω (L-N<20Ω)
|
20Ω
|
|
Nominal Test Current at 0Ω External Loop: Magnitude/Duration at 230V
|
20Ω: 6A/40ms 200Ω: 2A/20ms 2000Ω: 15mA/500ms
|
L-N: 6A/60ms N-PE: 10mA/approx.5s
|
20Ω: 6A/20ms
|
|
Accuracy
|
±3%rdg±4dgt (*1)
|
±3%rdg±6dgt (*1)
|
L-N: ±3%rdg±4dgt L-L: ±3%rdg±8dgt
|
|
PFC (L-PE) / PSC (L-N / L-L) (*2)
|
|
Function
|
PFC
|
PFC (ATT)
|
PSC
|
|
Rated Voltage
|
230V (50/60Hz)
|
L-N: 230V (50/60Hz) L-L: 400V (50/60Hz)
|
|
Operating Voltage
|
100 - 280V (45 - 65Hz)
|
100 - 500V (45 - 65Hz)
|
|
Range (Auto-Ranging)
|
2000A/20kA
|
2000A/20kA (L-N<20Ω)
|
2000A/20kA
|
|
Nominal Test Current at 0Ω External Loop: Magnitude/Duration at 230V
|
20Ω: 6A/40ms 200Ω: 2A/20ms 2000Ω: 15mA/500ms
|
L-N: 6A/60ms N-PE: 10mA/approx.5s
|
20Ω: 6A/20ms
|
|
Phase Rotation
|
|
Operating Voltage
|
50 - 500V, 45 - 65Hz
|
|
Remarks
|
Correct phase sequence: displayed "1.2.3" and mark Reversed phase sequence: displayed
"3.2.1" and mark
|
|
Volts
|
|
Function
|
Volts
|
Frequency
|
|
Measuring range
|
0 - 500V
|
45 - 65Hz
|
|
Accuracy
|
±2%rdg±4dgt
|
±0.5%rdg±2dgt
|
|
General
|
|
Applicable standards
|
IEC 61010-1 CAT III 300V (500V L to L), IEC 61010-031, IEC 61557-1, 3, 7, 10, IEC
60529 (IP54), IEC 61326 (EMC)
|
|
Power source
|
1.5V AA batteries × 6 *Use of alkaline batteries (LR6) is recommended.
|
|
Dimensions
|
84 (L) × 184 (W) × 133 (D) mm
|
|
Weight
|
860g (including batteries)
|
|
Accessories included
|
Main cord (*3) Distribution board test lead (*4) 9155 (Shoulder strap)
9156 (Soft case) LR6 (Battery) × 6, Instruction manual
|